Input Output module - WuT Web IO 57738 Configuration
Navigate to the W&T Web-IO website and apply the following settings:
Basic settings
Network
Configure the static IP settings
Enforce HTTPS for access to the website
Disable ports for device information, reset & update services
Inputs / Outputs
For each Input (optional):
Set the input filter
Inverse signal
Activate bi-direction counting + inactivity timeout
For each Output (optional):
Invert Output
Activate puls mode : A ‘set’ sent by the API, now results in a pulse. Note that this is only necessary if more accurracy is required than using the API’s ‘pulse’ method or for pulses <1s or >5s
Password
Set strong password for Administrator and Operator
Websites
Home
Disallow output switching & counter clearing (note that this can be done with the help of an opcua client)
Communication paths
Mail
Deactivate the option to send a mail
Box-to-box
Deactivate this option
MQTT
Deactivate this option
REST
Deactivate this option
Web API
Deactivate this option
Socket API
Deactivate this option
Modbus TCP
Deactivate this option
OPC DA
Deactivate this option
OPC UA
Activate this option
Port: 4840
Username: DeviceModule1
Password: as proposed by the ALIOT webportal
Authentication procedure: Sign & Encrypt
Security policy: Basic256 - SHA256
Enable access to all Outputs
SNMP
Deactivate this option
Syslog
Deactivate this option
FTP
Deactivate this option