Input Output module - WuT Web IO 57738 Configuration

Navigate to the W&T Web-IO website and apply the following settings:

Basic settings

Network

  • Configure the static IP settings

  • Enforce HTTPS for access to the website

  • Disable ports for device information, reset & update services

Inputs / Outputs

For each Input (optional):

  • Set the input filter

  • Inverse signal

  • Activate bi-direction counting + inactivity timeout

For each Output (optional):

  • Invert Output

  • Activate puls mode : A ‘set’ sent by the API, now results in a pulse. Note that this is only necessary if more accurracy is required than using the API’s ‘pulse’ method or for pulses <1s or >5s

Password

  • Set strong password for Administrator and Operator

Websites

Home

  • Disallow output switching & counter clearing (note that this can be done with the help of an opcua client)

Communication paths

Mail

  • Deactivate the option to send a mail

Box-to-box

  • Deactivate this option

MQTT

  • Deactivate this option

REST

  • Deactivate this option

Web API

  • Deactivate this option

Socket API

  • Deactivate this option

Modbus TCP

  • Deactivate this option

OPC DA

  • Deactivate this option

OPC UA

  • Activate this option

  • Port: 4840

  • Username: DeviceModule1

  • Password: as proposed by the ALIOT webportal

  • Authentication procedure: Sign & Encrypt

  • Security policy: Basic256 - SHA256

  • Enable access to all Outputs

SNMP

  • Deactivate this option

Syslog

  • Deactivate this option

FTP

  • Deactivate this option