.. _DeviceConfiguration_Gen2: ############################################## Alphatronics AP298, AP338, AP286 Configuration ############################################## 1. Configure the **Operating settings** of moxa module via its web interface - Operation mode: TCP Server Mode - Local TCP port: 4002 - Max connection: 4 - Delimiter 1: 23 - Ignore jammed ip: yes .. image:: /content/HALAPI/DeviceConfiguration/MoxaConfig_OperatingSettings_Screenshot.png 1. Configure the **Serial settings** of moxa module via its web interface - Baudrate: 19200 - Data bits: 8 - Stop bits: 1 - Parity: None - Flow control: RTS/CTS - Fifo: Enable - Interface: RS-485 2-Wire .. image:: /content/HALAPI/DeviceConfiguration/MoxaConfig_SerialSettings_Screenshot.png 3. Add a gen2 device to the device module in ALIOT webportal - Device type: AP286 / AP338 / AP298 - Interface: tcp/Ip - IP address: het IP address of the moxa module - IP Port: 4002 (default) - Port: /tmp/port0 (moxa serial port) - Serialnumber: serialnumber of the gen2 device - RS485 Address: RS485 address of the gen2 device - check 'Activated' checkbox .. note:: - Always start with /tmp/port0 as Port for the devices attached to the first moxa module. Select port /tmp/Port1 for the second moxa module, and repeat this for other moxa modules. - Never give 2 devices the same RS485 address on the same rs485 bus connected to the moxa module (module serial port) Troubleshooting *************** * Check you communication with the Gen2Manager tool using a separate moxa module (mapped to your pc with nport admin) * Use the 'health check' button in the device module info panel in the ALIOT portal, to test if the gateway can communicate with the gen2 device * Use the **Detect Port** command in the device module command panel to check if the moxa serial ports are available on the gateway * Restarting the device module via the device module command panel may be required after configuring a new gen2 device to enable connection with the recently created moxa serial port